Calculate the required ventilation area, number of air bricks, and spacing for suspended timber floors — fully compliant with UK Building Regulations Approved Document C.
Calculate your underfloor ventilation requirements
Enter your floor dimensions and conditions below. We’ll calculate the minimum free ventilation area required, number of air bricks needed, and recommend a suitable layout — all to Approved Document C standards.
Floor & building details
All fields used to calculate ventilation requirements
Internal floor area of the suspended timber floor zone.
Total length of external walls the floor runs alongside. Usually 2×(length + width) minus any internal party walls.
Measured from ground level to the underside of floor joists. Minimum 150mm required by regulations.
Wetter ground conditions require additional ventilation above the minimum requirement.
Party walls shared with neighbours reduce the number of external walls available for air bricks.
Standard clay 215×65mm is most common for Victorian / Edwardian properties.
Ventilation Requirements
Based on Approved Document C, UK Building Regs
Enter your floor dimensions, site conditions, and air brick type, then click Calculate to see your ventilation requirements.
Underfloor ventilation explained
Adequate underfloor ventilation prevents moisture build-up, protects timber joists from rot, and maintains healthy indoor air quality — all governed by UK Building Regulations.
Why Ventilate?
Without adequate airflow, moisture vapour rising from the ground becomes trapped beneath a suspended floor, causing timber rot, fungal decay, and structural damage. Proper ventilation creates cross-flow to carry moisture away.
Building Regulations
Approved Document C (Site preparation and resistance to contaminants and moisture) requires a minimum free area of 1,500mm² per metre run of external wall, with cross-ventilation paths no longer than 2 metres without a break.
Air Brick Types
Standard clay air bricks (215×65mm) provide around 3,250mm² of free area. Double-course or terracotta bricks offer more free area per opening. Choose to match your existing brickwork bond and course height.
Sleeper Walls
Internal sleeper (or honeycomb) walls supporting floor joists must include openings to allow air to pass through the void. Without cross-ventilation, isolated pockets of damp air cannot escape even with external air bricks present.
Approved Document C requirements
The table below summarises the key ventilation requirements from Approved Document C for suspended timber ground floors.
| Requirement | Minimum standard | Notes |
|---|---|---|
| Free ventilation area per metre run of wall | 1,500mm² / metre | Applies to each external wall the floor abuts |
| Minimum void height (ground to joist underside) | 75mm (absolute min); 150mm preferred | 75mm with ground DPC; 150mm without |
| Maximum distance for air to travel | 2 metres without obstruction | Sleeper walls must have openings every 2m |
| Air brick position | Above external ground level DPC | Minimum 75mm above finished ground level |
| Ventilation with ground DPM installed | Minimum 500mm² / metre run | Reduced rate acceptable where DPM covers entire ground area |
| Ventilation for high moisture ground | Enhanced — designer’s specification | Consult BS 5250 and structural engineer |
Source: Approved Document C — Site Preparation and Resistance to Contaminants and Moisture (2004, amended 2013). Always verify requirements with your local building control office.
Regulation-compliant results in seconds
Our calculator applies the Approved Document C formula — 1,500mm² of free area per metre of exposed wall — and then accounts for your ground conditions, building type, and DPM status to recommend the exact number and distribution of air bricks.
We also flag any compliance issues with your void height and provide a wall layout diagram showing where to position your air bricks for optimal cross-ventilation.
- ✓Approved Document C minimum free area formula applied
- ✓Ground condition multipliers for wet / clay sites
- ✓Air brick count per wall with layout visualisation
- ✓Void height compliance check (150mm minimum)
- ✓Sleeper wall cross-ventilation openings calculated
- ✓DPM reduction factor correctly applied
Practical Advice for the Underfloor ventilation calculator Complete Overview
What this calculator does
The idea behind the Underfloor ventilation calculator is simple: give everyone, from beginners to experienced users, a tool that makes underfloor ventilation quick and transparent. Every field is clearly labelled and nothing sits behind a paywall.
Who it helps
Site managers, builders and contractors and self-builders often turn to calculators like this one. Matching your own situation to the inputs takes only a moment, and you can repeat the process whenever your circumstances change. It often comes into play when estimating materials for a project, planning a loft or extension and comparing two design options, because a reliable figure for underfloor ventilation prevents costly second-guessing.
Getting accurate results
Preparation pays off here. Try to sketch the area before entering numbers, then add a sensible allowance for waste. After that, enter the numbers in the Underfloor ventilation calculator, read the answer, and repeat with a variation to test how stable the outcome really is.
Mistakes to avoid
When results seem off, the cause is frequently using nominal sizes instead of actual sizes or skipping a final site measurement. Re-reading your inputs line by line is the quickest way to find and fix either one.
Reading your result
Treat the output as one piece of evidence rather than a final verdict. Think about how underfloor and ventilation might change if your situation shifted, and repeat the calculation with updated values when it does. Because the calculation runs instantly in your browser, you can test as many scenarios as you like without any limit. Share the page with colleagues, friends or family if they are working through underfloor ventilation as well. Keeping a short note of each result makes it easy to compare options and explain your reasoning to others. Clear inputs lead to clear answers, so take a few extra seconds to read each label on the calculator before typing.
A note on accuracy
This Underfloor ventilation calculator gives planning estimates only. Confirm final quantities on site and follow building regulations and professional advice for structural or safety-critical work.
What Underfloor Ventilation Does
A suspended timber or block-and-beam floor sits over a void, and that void needs a constant flow of air. Without it, moisture builds up, joists and wall plates rot, and the floor can fail years before its time. Ventilation works by putting airbricks in opposite external walls so air flows across the void and carries the moisture out. The calculator on this page works out how much open area you need and how many airbricks that means, but the numbers only help if the vents are in the right places and are not blocked.
The Approved Document C Rule: The Greater of Two Figures
Approved Document C sets the amount of ventilation for a suspended floor as the greater of two figures: 1,500 mm² of free opening area for every metre run of external wall, or 500 mm² for every square metre of floor area. You must work out both numbers and use the larger one. Free area is the area of the holes in the airbrick, not the size of the brick itself, so a brick that measures 190 × 65 mm on the wall may only give 1,100 mm² of free area. That distinction is the reason a count based on the brick size alone always comes out too low.
Worked example: a 40 m² floor with 20 m of external wall
For a floor of 40 m², the floor-area figure is 40 × 500 = 20,000 mm². For 20 metres of external wall, the wall figure is 20 × 1,500 = 30,000 mm². The greater figure is 30,000 mm², so that is the opening area required. Using 190 × 65 mm airbricks with a free area of 1,100 mm² each, the number needed is 30,000 ÷ 1,100 = 27.27, which rounds up to 28 airbricks. You always round up: 27 airbricks would give 29,700 mm², which is 300 mm² short of the requirement.
Two more worked examples
A 60 m² floor with 24 m of external wall needs 60 × 500 = 30,000 mm² by floor area and 24 × 1,500 = 36,000 mm² by wall length, so the requirement is 36,000 mm², which is 36,000 ÷ 1,100 = 32.73, rounded up to 33 airbricks. A smaller 25 m² floor with 12 m of wall needs 25 × 500 = 12,500 mm² by floor area and 12 × 1,500 = 18,000 mm² by wall length, so the requirement is 18,000 mm², which is 18,000 ÷ 1,100 = 16.36, rounded up to 17 airbricks. In both cases the wall figure is the larger one, which is usual for long, narrow floors; for a large square floor the floor-area figure can take over.
Airbrick Free Areas: The BS 493 Table
BS 493:1995 +A1:2010 gives the free area of standard airbricks, and it is the free area, not the brick size, that counts towards the Approved Document C total. The table below shows the size the trade uses most often. Other sizes exist, and their free areas differ, so always use the manufacturer’s stated free area for the brick you are actually buying rather than guessing from the dimensions.
| Airbrick size | Free area (BS 493) | What it is used for |
|---|---|---|
| 190 × 65 mm | 1,100 mm² | The standard clay or plastic airbrick for a single-brick wall |
A 190 × 65 mm brick has a face area of 12,350 mm², but its holes only add up to 1,100 mm², which is less than a tenth of the face. That is why counting bricks instead of free area is the most common mistake in sub-floor ventilation: 28 bricks sounds like a lot, but it is only 30,800 mm² of opening, and 28 bricks counted at face area would look like 345,800 mm², which is more than ten times the real figure.
Where the Vents Go: Opposing Walls, Spacing and Sleeper Walls
Air needs a route through the void, so vents must be in opposing external walls to create cross-ventilation. Vents on one wall only leave the far side of the void still, and the floor above it will stay damp. Approved Document C guidance puts vents at no more than 2 m centres along the wall, so a 20 m wall run needs vents at 0, 2, 4, 6, 8, 10, 12, 14, 16, 18 and 20 metres — 11 positions — even if the total free area could be provided by fewer, larger vents. Sleeper walls inside the void must have openings in them too, or they block the airflow and split the void into separate still pockets. Each pocket then needs its own vents, which is why a floor with several sleeper walls can need more airbricks than the area calculation alone suggests.
Telescopic Liners, Flood Extensions and Blocked Vents
In a cavity wall the airbrick in the outer leaf must connect through the cavity to the void, and that is what a telescopic liner does: it is an adjustable sleeve that bridges the cavity so air does not get lost inside it. Where a floor is at risk of flooding, the vent can be raised with a flood extension so the opening sits above the expected water level instead of letting water straight into the void. The most common failure, though, is simpler: vents get blocked by soil piled against the wall, by paving laid above the vent, by paint, or by debris inside the void. A blocked vent gives no ventilation at all, so the first step on any damp floor is to walk round the outside and check that every vent is clear and below the damp-proof course.
Choosing Vent Types
The two common choices are a standard clay or plastic airbrick and a periscope vent. A periscope vent, such as the Rytons Periscope Vent used with a Multifix Air Brick, is a tall unit that carries the air path up through a thick wall or past an obstruction, and it is the usual choice for block-and-beam floors where the void is deep, or where the external ground level is high. A standard airbrick is enough for a straightforward suspended timber floor with a normal wall. Whichever type you use, the free area is what counts: a periscope vent’s stated free area is the figure to put into the calculation, and it is often lower than the airbrick it is paired with, so the vent, not the brick, can be the limiting factor.
A Three-Step Way to Check an Existing Floor
The method used by retrofit specialists has three steps. First, work out the required opening area from the floor area and the wall run, using the greater of the two Approved Document C figures, as in the worked examples above. Second, audit what is already there: count the airbricks, note their size, and multiply by the BS 493 free area for that size — a 190 × 65 mm brick gives 1,100 mm². Third, compare the two numbers and work out the shortfall, then decide whether to add more airbricks of the same type or to upgrade to a type with a larger free area. For example, a floor needing 30,000 mm² that already has 10 airbricks at 1,100 mm² has 11,000 mm² and is 19,000 mm² short, which needs 18 more airbricks of the same size.
Do I need ventilation under a concrete floor?
No. A solid concrete ground floor has no void to ventilate, so the Approved Document C figures do not apply to it. They apply to suspended timber floors and to block-and-beam floors, which both have a void underneath.
Can I put vents in only one wall?
No. Air needs to flow across the void, which means openings in opposing walls. Vents in one wall alone will not ventilate the far side of the floor, and the joists there will still be at risk of rot.
What if my airbricks are below ground level?
Then they are not ventilating anything and they are letting water in. The ground level outside should be at least 150 mm below the damp-proof course, and the vents should sit above the ground. If the ground has been built up, dig it back or fit a periscope vent with a flood extension to raise the opening.
Underfloor ventilation FAQs
Explore our other free tools
From damp calculation to U-value tools — all UK-specific, all completely free.
