Convert kVA to amps, or amps to kVA, on a three phase supply. Enter the line-to-line voltage and get the current instantly, with kW from power factor and the working shown.
Convert kVA to Amps
Pick a direction, enter your value and the line-to-line voltage, and the converter does the three phase maths. Add a power factor if you also want the real power in kW.
Three Phase kVA and Amps Calculator
Convert in either direction using the √3 formula.
How the Conversion Works
The three phase formulas behind the result
kVA to Amps
Amps = kVA × 1,000 ÷ (√3 × V). At 415V, 100 kVA gives 100,000 ÷ (1.732 × 415), which is about 139.1 A.
Amps to kVA
kVA = √3 × V × amps ÷ 1,000. At 415V, 100 A gives 1.732 × 415 × 100 ÷ 1,000, which is about 71.9 kVA.
Use Line-to-Line Voltage
Three phase formulas use the voltage between two phases, not the phase-to-neutral voltage. Phase-to-neutral is the line voltage divided by 1.732.
Add Power Factor for kW
kW = kVA × power factor. The power factor does not change the amps for a given kVA, only how much of it is real power.
Getting the Most From the kVA to Amps Three Phase Converter In-Depth Notes
What this calculator does
A reliable method for kva to amps three phase converter saves effort every time you return to it. The kVA to Amps Three Phase Converter on this page behaves consistently from one visit to the next, so identical inputs always give identical results.
Who it helps
This tool is useful for engineers, online shoppers and travellers. Each group approaches kva to amps three phase converter with different priorities, yet the same careful inputs lead to a result everyone can rely on. Real-world uses range from reading a technical sheet, doing homework and checking measurements for a project. These examples show why an accessible tool for kva to amps three phase converter is so valuable.
Getting accurate results
Follow a simple routine each time you work out kva to amps three phase converter: check the unit you start with, enter your values carefully, and then compare with a rough estimate. Repeating the same routine builds a reliable habit and makes your results easier to compare later.
Mistakes to avoid
When results seem off, the cause is frequently reading the wrong unit label or rounding too early. Re-reading your inputs line by line is the quickest way to find and fix either one.
Reading your result
A good habit is to sense-check every answer. Ask whether it is the right size, whether amps and kva have been entered sensibly, and whether rounding could be hiding something important. If you are unsure about a value, try a low and a high estimate and see how far apart the answers are. Bookmark this page so the kVA to Amps Three Phase Converter is always one tap away when you need it again. Keeping a short note of each result makes it easy to compare options and explain your reasoning to others.
A note on accuracy
Please treat the outcome from the kVA to Amps Three Phase Converter as a helpful estimate. Your own circumstances may differ, so verify key figures with a trusted source before relying on them for a major decision.
kVA to Amps Chart
Line current in amps for common kVA ratings on a three phase supply at 400V, 415V and 480V.
| kVA | Amps at 400V | Amps at 415V | Amps at 480V |
|---|---|---|---|
| 5 kVA | 7.22 A | 6.96 A | 6.01 A |
| 10 kVA | 14.43 A | 13.91 A | 12.03 A |
| 15 kVA | 21.65 A | 20.87 A | 18.04 A |
| 20 kVA | 28.87 A | 27.82 A | 24.06 A |
| 30 kVA | 43.30 A | 41.74 A | 36.08 A |
| 50 kVA | 72.17 A | 69.56 A | 60.14 A |
| 63 kVA | 90.93 A | 87.65 A | 75.78 A |
| 100 kVA | 144.34 A | 139.12 A | 120.28 A |
| 200 kVA | 288.68 A | 278.25 A | 240.56 A |
| 500 kVA | 721.69 A | 695.62 A | 601.41 A |
Values are rounded to two decimal places and assume a balanced three phase load. For equipment selection, always check the manufacturer’s rating and relevant wiring regulations.
kVA to Amps FAQ
Answers to the most frequently asked questions about converting kVA to amps on a three phase supply.
Multiply the kVA by 1,000, then divide by the square root of 3 (1.732) multiplied by the line-to-line voltage. For example, 100 kVA at 415V is 100,000 divided by (1.732 × 415), which gives about 139.1 amps per phase.
kVA equals the square root of 3 (1.732) multiplied by the line-to-line voltage and the current in amps, divided by 1,000. For example, 100 amps at 415V gives about 71.9 kVA.
No. kVA is apparent power, so converting between kVA and amps only needs the voltage. Power factor is only needed to convert kVA to kW, where kW equals kVA multiplied by the power factor.
Use the line-to-line voltage, which is nominally 400V in the UK, although 415V is still widely quoted and used on equipment ratings. Check the nameplate or supply details for the figure that applies to your installation.
kVA is apparent power, the total power drawn from the supply, while kW is real power, the part that does useful work. kW equals kVA multiplied by the power factor, so for a power factor of 0.8, a 100 kVA load delivers 80 kW.